Valere’s Line Power Solutions are industry-leading
DC-DC converter systems optimized for the demanding power needs of today’s
last mile communications systems.
The Head End Converter System is a compact 2RU system
consisting of 14 converter modules and an optional 1RU fan shelf. Each
module contains three 100VA DC-DC converters. In addition, the Head End
Converter System provides up to 42 individual 100VA outputs at either
-190Vdc, +/-130Vdc, or +/-190Vdc per shelf.
|
|
 |
 |
|
| |

-
Overlays and New Builds
The Head End Converter System is ideal for new FTTX deployment.
Its small compact size maximizes space available for broadband
equipment and new revenue services. Its modular “pay as you
grow” concept helps minimize installation and operating cost
by sizing the power system to support specific loads.
-
Expansions
The Head End Converter System is easily expanded from a single,
triple 100VA converter up to 14 triple 100VA converters. The modules
are hot swappable and easily field installed.
- -48Vdc to -190Vdc, +/-130Vdc, or +/-190Vdc Power Modules
- Simplified Output Distribution
- 42 Feeds in Only 2RU of Rack Space
|
|
|

More Room for Revenue
Equipment Each 2RU shelf accommodates
up to 4,200VA of -190Vdc, +/-130Vdc, or +/-190Vdc power.
Reduced Installation and Maintenance
Costs Lightweight chassis for easy rack mounting. Fully
connectorized input and output connections reduces field wiring time
and errors.
Robust Design Each
shelf supports up to 42 100VA outputs. Each converter has an internal
VA protection that limits output to 100VA. The converters are Ground
Fault protected to less than 5mA.
Better Quality of Service
With efficiencies greater than 90%, the Head End Converter System
reduces thermal load on outside plant enclosures while reducing the amount
of incoming energy to support the configuration.
Scalable Solution
The modular concept allows the system to grow from 300VA up to 4,200VA
in a single 2RU shelf. Multiple shelves may be combined for large scale
deployment.
|
|
| |

POWER SHELF SPECIFICATIONS
DIMENSIONS
-
Height: 87.63mm (3.45")
-
Width: 546.10mm (21.5")
-
Depth: 304.80mm (12.00")
AIRFLOW
|
-
External, 100LFM min., bottom to top provided by
customer
-
Available 1RU fan tray (Contact your local Valere
sales representative for details).
TEMPERATURE RANGE
-
-40°C to +85°C storage
- -40°C to +75°C operating
|
| INPUT VOLTAGE |
- -40V to -60V, 54V Standard
|
INPUT POWER
|
- Up to 333W per converter module, up to 4,667W per power shelf
|
INPUT CURRENT |
- Up to 8.5 amp per converter module, up to 120
amps per power shelf
- Dual A/B Feed up to 60A per feed
|
| EFFICIENCY |
|
|
CONNECTORS
|
All connectors are rear mounted on the backplane
-
DC Output Connector(s): 3 pair per converter
modules, 42 pair per power shelf
-
DC Input Connector: Dual input, bulk
feed via double hole lug. Accepts up to 4 gauge input wiring.
-
Secondary Earth Grounding: Dual connections,
double hole lug. Accepts up to 4 gauge ground connection.
-
Alarm Connections: Six pin connector,
two form C alarm closures.
- Optional NIC: Provides remote interface and full diagnostic
and system status information on converter modules.
FRONT PANEL LEDs |
- FEED 1 OK (GRN), FEED 2 OK (GRN), FEED 3 OK (GRN), ALARM (RED)
|
AGENCY CERTIFICATIONS
-
UL/cUL 60950-1
- NEBS Level 3 Approvals
- GR1089
|
|
|
|

TRIPLE CONVERTER MODULE INPUT SPECIFICATIONS
INPUT VOLTAGE RANGE
INPUT CURRENT LIMIT
INPUT PROTECTION
TRIPLE CONVERTER MODULE OUTPUT SPECIFICATIONS
| OUTPUT VOLTAGE |
(Dual A/B feed per converter module)
- -190V
system: -190V nom.
- +/-130V system: +/-130V nom.
- +/-190V system: +/-190V nom.
|
| OUTPUT PROTECTIONS |
- 100VA power limit
- 5mA Ground fault protections
|
| EFFICIENCY |
- -190V: 90% nominal efficiency
- +/-130V: 90% nominal efficiency
- +/-190V: 90% nominal efficiency
|
| LED INDICATORS |
- Separate LED indication for each feed pair
- Alarm indication for input voltage
- Alarm LED indicates module fault condition
|
| PROTECTIONS |
- Overtemperature protection
- Low airflow protection
- Output overload protection
- Input low voltage protection
- Input reversal protection
|
|
|